Corrosion in RJ11 / RJ45 Connectors

 
Post new topic   Reply to topic    DComTalk.com Forum Index -> Cabling
Author Message
bob.elliot@ieee.org
Guest





Posted: Thu Apr 14, 2005 9:51 am    Post subject: Corrosion in RJ11 / RJ45 Connectors Reply with quote

Has anyone encountered corrosion in RJ11 / RJ45 jack / plugs? I think
this effect might be mostly limted to areas closer to the sea, high
humidity areas, in higher temperature areas and where there might be
additional airborne pollutants. Florida and Hawaii come to mind.

Also, the use of voice on the line (with voltages of up to +/- 48 volts
- ?) may worsen electrolytic corrosion - I don't think it's a galvanic
corrision effect. Not sure.

I'm wondering what will happen with the planned Power over the
Ethernet. That will use 48 volts across pins of the RJ45 connectors.

Thanks for any comments you may have,

Regards,

Bob Elliot
Back to top
James Knott
Guest





Posted: Thu Apr 14, 2005 10:46 am    Post subject: Re: Corrosion in RJ11 / RJ45 Connectors Reply with quote

bob.elliot@ieee.org wrote:

Quote:
Has anyone encountered corrosion in RJ11 / RJ45 jack / plugs? I think
this effect might be mostly limted to areas closer to the sea, high
humidity areas, in higher temperature areas and where there might be
additional airborne pollutants. Florida and Hawaii come to mind.

On it's own, gold doesn't corrode. However, some connectors might be a bit
cheap with the gold.
Quote:

Also, the use of voice on the line (with voltages of up to +/- 48 volts
- ?) may worsen electrolytic corrosion - I don't think it's a galvanic
corrision effect. Not sure.

I'm wondering what will happen with the planned Power over the
Ethernet. That will use 48 volts across pins of the RJ45 connectors.

It's not the voltage that causes that, it's the current that caused the ion
migration. Also, higher voltages tend to penetrate the corrosion. I
believe the phone companies refer to that as "sealing current".
Back to top
Dale Farmer
Guest





Posted: Thu Apr 14, 2005 8:35 pm    Post subject: Re: Corrosion in RJ11 / RJ45 Connectors Reply with quote

"bob.elliot@ieee.org" wrote:

Quote:
Has anyone encountered corrosion in RJ11 / RJ45 jack / plugs? I think
this effect might be mostly limted to areas closer to the sea, high
humidity areas, in higher temperature areas and where there might be
additional airborne pollutants. Florida and Hawaii come to mind.


Seen it in wet locations. Kitchens, laundry rooms, wet basements
and the like. The wiping action of plugging it in usually scrapes enough
of the corrosion off to make a connection. Of course ones that are
gold plated too a sufficient thickness are not going to corrode. Don't
buy cheap connectors for these locations. Usually the problem with
these connectors are the corrosion inside on the copper wires has
caused problems. You can get various compounds for sealing these
in your local auto parts store. Look under the battery connector
sealing sprays.

--Dale
Back to top
Dmitri(Cabling-Design.com
Guest





Posted: Fri Apr 15, 2005 6:48 pm    Post subject: Re: Corrosion in RJ11 / RJ45 Connectors Reply with quote

bob.elliot@ieee.org wrote:




Quote:
Has anyone encountered corrosion in RJ11 / RJ45 jack / plugs? I think
this effect might be mostly limted to areas closer to the sea, high
humidity areas, in higher temperature areas and where there might be
additional airborne pollutants. Florida and Hawaii come to mind.

Also, the use of voice on the line (with voltages of up to +/- 48 volts
- ?) may worsen electrolytic corrosion - I don't think it's a galvanic
corrision effect. Not sure.

I'm wondering what will happen with the planned Power over the
Ethernet. That will use 48 volts across pins of the RJ45 connectors.

Thanks for any comments you may have,

Regards,

Bob Elliot

Does not have to be Florida or Hawaii: in one instance here in PA all it
took was a cleaning lady, who decided the faceplate is dirty. We could not
identify the actual solution she used, but the RJ11 plug got totally
destroyed. Upon taking it from the jack all the contact material simply
fell down in a form of a black powder. That effectively knocked off a
digital PBX phone that uses constant 48V (as oppose to "smart" 48V of PoE
that you’ve mentioned here). Much less of a contact problem would render
PoE circuit dead because before applying the full power an 802.3af power
hub/switch sends a weak-current polling signal and looks for a response
from the terminal equipment.

--
Dmitri Abaimov, RCDD
http://www.cabling-design.com
Cabling Forum, color codes, pinouts and other useful resources for
premises cabling users and pros
http://www.cabling-design.com/homecabling
Residential Cabling Guide
-------------------------------------


##-----------------------------------------------#
Article posted with Cabling-Design.com Newsgroup Archiv
http://www.cabling-design.com/forum
no-spam read and post WWW interface to your favorite newsgroup -
comp.dcom.cabling - 1622 messages and counting
##-----------------------------------------------##
Back to top
Thomas Beneken
Guest





Posted: Sat Apr 16, 2005 10:30 am    Post subject: Re: Corrosion in RJ11 / RJ45 Connectors Reply with quote

Bob,

we used to make NTU's for Irish Telecom. Corrosion was a challenge.

You can cover the contact surface with a very thin layer of wax or seal the
jack's arperture with a jelly.

Regards
Thomas

<bob.elliot@ieee.org> schrieb im Newsbeitrag
news:1113472285.663051.281720@l41g2000cwc.googlegroups.com...
Quote:
Has anyone encountered corrosion in RJ11 / RJ45 jack / plugs? I think
this effect might be mostly limted to areas closer to the sea, high
humidity areas, in higher temperature areas and where there might be
additional airborne pollutants. Florida and Hawaii come to mind.

Also, the use of voice on the line (with voltages of up to +/- 48 volts
- ?) may worsen electrolytic corrosion - I don't think it's a galvanic
corrision effect. Not sure.

I'm wondering what will happen with the planned Power over the
Ethernet. That will use 48 volts across pins of the RJ45 connectors.

Thanks for any comments you may have,

Regards,

Bob Elliot
Back to top
TheCablingGuy
Guest





Posted: Mon Apr 18, 2005 4:20 pm    Post subject: Re: Corrosion in RJ11 / RJ45 Connectors Reply with quote

James Knott wrote:
Quote:
bob.elliot@ieee.org wrote:


Has anyone encountered corrosion in RJ11 / RJ45 jack / plugs? I think
this effect might be mostly limted to areas closer to the sea, high
humidity areas, in higher temperature areas and where there might be
additional airborne pollutants. Florida and Hawaii come to mind.


On it's own, gold doesn't corrode. However, some connectors might be a bit
cheap with the gold.

As often before your chances off success is better with a quality system.


I only remember a few cases across the thousands of quality connectors I
have installed and serviced.
All of them could be linked to cleaning or other physical contamination



--
The Cabling Guy
I only express my own personal opinion on Usenet.
Back to top
Watson A.Name - \"Watt Su
Guest





Posted: Tue Apr 19, 2005 4:20 pm    Post subject: Re: Corrosion in RJ11 / RJ45 Connectors Reply with quote

<bob.elliot@ieee.org> wrote in message
news:1113472285.663051.281720@l41g2000cwc.googlegroups.com...
Quote:
Has anyone encountered corrosion in RJ11 / RJ45 jack / plugs? I think
this effect might be mostly limted to areas closer to the sea, high
humidity areas, in higher temperature areas and where there might be
additional airborne pollutants. Florida and Hawaii come to mind.

Also, the use of voice on the line (with voltages of up to +/- 48
volts
- ?) may worsen electrolytic corrosion - I don't think it's a galvanic
corrision effect. Not sure.

You shouldn't allow your connectors to get wet.

I have a problem with 66 block corrosion, caused mostly, I believe, from
condensation. The room also has a custodian sink and washer and dryer
in it.

I had a problem with corrosion in a classroom. It's the chemistry lab.
You know that the jacks and plugs have gold plating, which protects them
against corrosion. Well, it takes a lot to corrode gold. I guess the
chemicals in that lab must have been vapors from both nitric and
hydrochloric acids, which make aqua regia, IIRC. The chairs were up on
the desks, and I noticed that the chairs' chrome legs were corroded
badly, mostly brown rust.

Quote:
I'm wondering what will happen with the planned Power over the
Ethernet. That will use 48 volts across pins of the RJ45 connectors.

That's already being used. Without problems.

Our digital PBX uses 54V (which is what 48V batteries put out) at up to
150mA. We don't have any problems at all with power over 66 blocks, 110
blocks, RJ-11 or RJ-45. The telcos use 108V across the pair with T1
spans.


Quote:
Thanks for any comments you may have,

Regards,
Bob Elliot
Back to top
 
Post new topic   Reply to topic    DComTalk.com Forum Index -> Cabling All times are GMT
Page 1 of 1

 
You cannot post new topics in this forum
You cannot reply to topics in this forum
You cannot edit your posts in this forum
You cannot delete your posts in this forum
You cannot vote in polls in this forum




VoIP Solutions: Telephone Systems Electronics Satellite TV Tech & Gadgets
Powered by phpBB